Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T11CM00423
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the desired maximum pressure drop for the gas piping; both 0.3" H2O and 0.5" H2O are called out on the drawing. 2. The gas piping chart shown on sheet M6.0 is not from the 2006 IFGC. 3. Show how the pipe was sized. The sizes appear to have been calculated using different developed pipe lengths. If so, indicate the length used for each load. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/26/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |