Permit Number: T11CM00423
Parcel: 12803078A

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T11CM00423
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the desired maximum pressure drop for the gas piping; both 0.3" H2O and 0.5" H2O are called out on the drawing.
2. The gas piping chart shown on sheet M6.0 is not from the 2006 IFGC.
3. Show how the pipe was sized. The sizes appear to have been calculated using different developed pipe lengths. If so, indicate the length used for each load.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2011 GERARDO BONILLA OUT TO CUSTOMER Completed