Permit Number: T11CM00419
Parcel: 13813001B

Address:
5701 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T11CM00419
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2011 GERRY KOZIOL WWM REVIEW Denied NEED WW/IWC REVIEW & APPROVAL OF SAND /OIL INTERCEPTOR FOR CAR WASH- TOM TOMCHAK- 443-6200- 5025 W INA RD
NEED WASTEWATER 5TH FLOOR CREDIT EVALUATION FOR ANY BLDGS DEMO'D WITH PLUMBING FIXTURES REMOVED
04/04/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Car Wash - 5701 S. 12th Avenue
T11CM00419
Building Plan (2nd Review)

TRANSMITTAL DATE: April 4, 2011


1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until the development plan has been approved by all PDSD agencies..

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t11cm00419.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
04/07/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Can not approve the building plan until the development plan has been approved by all PDSD agencies.
2. Permit will not be issued without submission and approval of Special Inspector Certifications.
END OF REVIEW
04/12/2011 ROBERT SHERRY WATER REVIEW Approved
04/12/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. The sink and faucet (shown as Item #10 on sheet P2.1 and as "T" on sheets P1.0 and P1.1), are neither specified nor identified as complying with any material standards. [Provide material standards for all plumbing fixtures being provided by others. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Sections 301.1.1 and 401.1, UPC 2006.]
2. Comment not resolved; detail 200 is not coordinated with the plumbing plan. The detail tag on the plumbing plan points to a 300-gallon storage tank and one of the two water softener tanks but not to the water heater. Show how the two water softener tanks are to be plumbed. Indicate the route and termination point of the T&P relief for the water heater. [Provide a detail of the water softener and water heater installation, including the valves, temperature and pressure relief, and expansion tank. Reference: Sections 103.2.3, 605.5, and 608.3, UPC 2006.]
3. Comment not resolved. The submitted information consisted of a description of a control valve for two water softener tanks and an advertising sheet for Rheem-Ruud water heaters in general (i.e. no model number). [Provide the listing information for the water heater and water softener. Reference: Section 301.1, UPC 2006.]
04/12/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 04/12/2011,

Submit a copy of the approved and stamped Development Package for review and approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2011 DELMA ROBEY OUT TO CUSTOMER Completed
04/19/2011 SUE REEVES REJECT SHELF Completed