Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00408
Parcel: 103090800

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00408
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a cut sheet for the Hi/low Reverse Osmosis Water Cooler. Insure the installation meets all accessibility requirements of the 2006 IBC, Section 1109.5 and ICC (ANSI 117.1), Section 602
04/29/2011 ROBERT SHERRY WATER REVIEW Approved
04/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; a call-out for a PRV is still located on the water riser diagram (2/p1). [Clarify the location of the pressure reducing valve; detail4/p2 implies that it is located between the existing water meter and the existing reduced pressure-zone backflow preventer but the water riser diagram (2/p1) indicates that it is located inside the building, downstream of the first hose bibb. Reference: Sections 103.2.3 and 608.2, UPC 2006.]
2. Comment not resolved; indicate the size of the screws to be used to attach the water heater support to the wall. [Coordinate the water heater support design shown in detail 1/p2 with detail 29/a9.1. Reference: Section 103.2.3, UPC 2006.]
04/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The MSDS information that was provided is for the products manufactured by HJ3 but by themselves they do not provide sufficient information to evaluate the classification of the three rooms (106, 108, and 109) per Table 307.1(1), IBC 2006. Review the information shown in Section 307 and Table 307.1(1), IBC 2006 and provide the total quantities of all hazardous materials used or stored in rooms 106, 108, and 109. If the rooms do contain hazardous materials in quantities exceeding the amounts shown in Table 307.1(1), show how each room will comply with the exhaust requirements of Section 502, IMC 2006. [Provide information regarding the work being conducted in the production rooms (H2 and F1 occupancies), the materials being used and the quantities of materials being used and stored. Reference: Sections 502.8 and 502.9, IMC 2006.]
05/10/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Previous electrical plan review requested a description of the process to take place,this was not provided. The response indicates "see architectural response and MSDS sheets provided". Neither provides the process.
The MDSD sheet for one of the chemical used (HCRC-602A), Vinyl Ester Resin ,shows a flash point of 32C and 89F, and the directions for storage and handling call for the chemical to be kept away from hear,electric motors and source of ignition.Vapors may cause flash fire or ignite explosively.
Provide a letter describing the process of work with these chemicals and indicate how the process may apply to wiring methods concerning 2005 NEC, Article 500.

Ray T Majuta,
Elect Pln Ck,PDSD,
City of Tucson,
5/11/11
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/31/2011 CPIERCE1 OUT TO CUSTOMER Completed
05/31/2011 SUE REEVES REJECT SHELF Completed