Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2011 GERRY KOZIOL WWM REVIEW Denied NEED 3RD FLOOR CAPACITY REVIEW & APPROVAL
NEED WW 5TH FLOOR CREDIT EVALUATION
NEED 3RD FLOOR PCRWRD REVIEW OF LOCATION /METHOD OF CONNECTION TO PUBLIC SEWER- CHAD
AMATEAU
05/03/2011 RONALD BROWN ADA REVIEW Passed
05/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00401
636 N Av
Convert Office to Apt's


The electrical plans require Fault Current calculations, according to TEP Service Requirement Book, the utility can provide 120/240 v single phase with up to 22,000 to 42,000 AIC.


Ray Majuta
Elect Pln Ck,PDSD,
City of Tucson,
5/9/11
Ray.majuta@tucsonaz.gov
05/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T.1; CODE REVIEW: PROVIDE AN ACCESSIBILITY ANALYSIS IN THIS SECTION. PROVIDE VERBIAGE ADDRESSING 2006 IBC SECTION 1107.6.2 (TYPE A AND B UNITS), AND ANY APPLICABLE EXCEPTIONS FROM SECTION 1107.7, INCLUDING ACCESSIBLE ENTRANCES.
2. SHEET T.1; CODE REVIEW: UNDER "DESCRIPTION OF PROJECT", REVISE THE IBC REFERENCE TO 2006.
3. SHEET T.1; CODE REVIEW: PROVIDE VERBIAGE IN THE CODE REVIEW ADDRESSING THE EXCEPTION TO THE REQUIREMENT OF AN EMERGENCY ESCAPE ROUTE REFERENCED IN SECTION 1026.
4. SHEET S.2; DETAILS A AND B: A NOTE INDICATES "2X BLOCKING W/ 3-16d TO EACH STUD". VERIFY IF TOENAILING IS ALLOWED, AND INDICATE ON THE DETAIL.
5. SHEET S.2; FLOOR FRAMING PLAN KEYNOTES: NOTE 8 INDICATES 1/2" DIAMETER ANCHOR BOLTS AT 32" OC AT THE NEW STAIR STUD WALLS, WHILE DETAIL 1/S.1 INDICATES 3/16" SHOT PINS AT 16" OC. CLARIFY.
6. SHEET S.2; FLOOR FRAMING PLAN KEYNOTES: NOTE 12 INDICATES NEW FLOOR OPENINGS (14"X14") FOR MECHANICAL DUCTWORK. IS ANY ADDITIONAL FRAMING REQUIRED AROUND THESE OPENINGS? VERIFY.
7. SHEET S.2; DETAIL E: IS THIS DETAIL INDICATED ON THE FLOOR FRAMING PLAN? VERIFY.
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
05/11/2011 ROBERT SHERRY WATER REVIEW Approved
05/11/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code is either the 2006 Uniform Plumbing Code with Local Amendments or the 2006 Uniform Plumbing Code with Local Amendments, not the 2006 International Residential Code. This activity has been reviewed to the 2006 IPC.
2. Provide water isometrics and waste and vent isometrics. Reference: Section 106.3.1, IPC 2006.
3. Substitution of alternate piping materials (e.g. PEX instead of copper piping) will require a revision of the water pipe sizing to match the revised piping materials. Reference: Sections 106.3.1 and 604.1, UPC 2006.
4. Provide a cleanout at the base of each waste stack. Reference: Section 708.3.4, IPC 2006.
5. Clarify the 2-way cleanouts shown at the junctions of the building drains and the building sewer. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings. Reference: Sections 708.3.5 and 708.5, IPC 2006.
05/11/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The 2006 International Mechanical Code with Local Amendments and the 2006 International Energy Conservation Code with Local Amendments are the relevant codes for this project.
2. Provide a horizontal separation of at least ten feet between air intake openings and exhaust openings located less than two feet above the air intake openings. Reference: 401.4.1, IMC 2006.
3. Provide automatic or gravity dampers for all outdoor air intakes and exhaust outlets per Section 403.5, IECC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/12/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
05/12/2011 SUE REEVES REJECT SHELF Completed