Permit Number: T11CM00400
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00400
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2011 MARTIN BROWN FIRE REVIEW Approved
03/08/2011 GERRY KOZIOL WWM REVIEW Denied need wastewater 3th fl sewer capacitiy evaluation-740-0547
need wastewater IWC review & appraval of 2000 gal grease interceptor- Tom Tomchak- 443-6200- 5025 W Ina Rd
need DEQ review & approval for on-site private sewer revisions with private manhole- 33 N Stone Av, 7th fl-
243-7400
need copy of on-site private sewer revisions for base map update- private sewer revision connects to exsisting on-site private sewer.
03/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations and details for the following:
a. All fencing above 6'-0", masonry and chain link.
b. All new roof top mounted HVAC equipment
c. All suspended water heaters
2. Please provide all Special Inspection Certifications for review and approval as outlined on Sheet S0.
3. Please provide a letter to teh building official, Mr. Ron Boose, providing a list of all deferred submittals for the purpose of assessing addition plan review fees.
4. The structural calculations could not be reviewed because of the lack of foundation and roof framing key plans. Please provide such and resubmit.
5. Please provide a written response to all comments.
03/16/2011 ROBERT SHERRY WATER REVIEW Approved
03/16/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design for the mounting shelves for water heaters WH2, WH3, and WH4 and show how they are attached to the building structure. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Provide information to show that the hub drain (detail 5GP1) complies with Sections 411.1 and 804.1, UPC 2006.
3. Each piece of equipment requiring backflow protection shall be independently protected. Reference: Sections 602.2 and 603.0, UPC 2006, as amended by the City of Tucson.
4. A dual check valve (a Watts SD-3is not listed for health hazards) is not acceptable for protecting the water supply to a carbonator; provide a reduced pressure principle backflow preventer. Reference: Section 603.4.12, UPC 2006.
5. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
6. Clarify how the discharge of the trench drain for the dairy cooler complies with Section 801.2.2, UPC 2006.
7. Show that the floor drains used as indirect receptors for the temperature and pressure relief drains of water heaters WH1 in the pharmacy, WH3 in GR receiving, and the heat reclaim system (ST1, ST2, and WHG1) are capable of accommodating the flow without flooding or splashing. Reference: Section 804.1, UPC 2006.
8. Each vent for a combination waste and vent system shall be at least one-half of the cross-sectional area of the pipe being vented. Reference: Section 910.3, UPC 2006.
9. Provide an accessible cleanout in each vent of a combination waste and vent system. Reference: Section 910.6, UPC 2006.
10. Provide natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Verify that 5 PSIG gas is available for this activity. Reference: Section 1217.0, UPC 2006.
03/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide supporting documentation for the assembly U-factors for the exterior walls and the roof (see footnote b in your submitted envelope compliance certificate). Reference: Section 104.2, IECC 2006.
2. Provide calculations demonstrating adequate ventilation. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
3. Verify that the UPC/UPS room does not require ventilation per Section 502.4, IMC 2006.
4. Gas-fired convection ovens require a Type I hood; show how the convection oven located in the bakery complies with this requirement. Reference: Section 507.1, IMC 2006.
5. Section 507.2.2, IMC 2006, exception 3, allows the installation of a "single light-duty electric convection, bread, retherm, or microwave oven" without the requirement of installing a Type II hood. The Subway equipment plan indicates the installation of a light-duty bread oven, a microwave oven, and a rapid-cook oven. Determine which single appliance will not be located under a Type II hood.
03/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00400
455 E Wetmore RD
Walmart TI and Expansion

The Electrical Plans have been denied for the following:

1. Indicate on Sheet E2.3 , that in the MSB Electrical Room, Per NEC 2005 110.26.C.2, "doors to be equipped with panic
bars,or other devices that are normally latched but open under simple pressure".
2. The distances for clearances between MSB Section 2 and Panel H1A1-1 and 2 appears to be just over 2 feet. Per 2005 NEC 110.26.A.1, 4 feet is required per condition 3.
3. The distance between MSB Section 3 and Panels H1A1-1 and 2 appears to be 2.5 feet, and requires 4 feet per 2005 NEC 110.26.A.1.
4. The Equipment Bonding Jumper on Sheet E-4 on the grounding electrode system needs to be sized per 2005 NEC 250.102.C.

Please address each individually and stste how each was addressed.

R.T. Majuta
Elect Pln CK,PDSD,
City of Tucson,
3/28/11,
Ray.majuta@tucsonaz.gov
03/29/2011 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2011 CPIERCE1 OUT TO CUSTOMER Completed
04/21/2011 SUE REEVES REJECT SHELF Completed