Permit Number: T11CM00397
Parcel: 13505149X

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM00397
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SEE COMMENTS FOR PROJECT T11CM00396.
03/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
03/03/2011 JASON GREEN ENGINEERING REVIEW Denied DATE: February 7, 2011
REVIEWER: Jason Green, CFM
ACTIVITY: T11CM00396 (Building Plan) and T11CM00397 (Canopy)


SUMMARY: Engineering Division of Planning & Development Services Department has received the building plan (T11CM00396) and canopy plan (T11CM00397). Engineering Division does not recommend approval of the building plan applications at this time. The following items need to be addressed:


BUILDING PLAN COMMENTS:

1) Engineering could not verify that the building plan was in compliance with a stamped approved Development Plan Package (D10-0046). Please submit a copy of the stamped approved Development Plan, landscape, and NPPO plans with the next building plan submittal.

2) Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped Development Plan. Additional comments may be forthcoming.


GENERAL COMMENTS:

Please provide the building plan with a copy of the last approved Development Plan (D10-0046). Further comments may be generated upon resubmittal of the building plan review.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
03/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/03/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Sheets C100 and C111

The fuel canopy appears to have over 300 feet of hose lay from the farthest point to the existing hydrant. A new hydrant or fire sprinklers are required. See IFC 508.5.1 as amended.
03/03/2011 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: QuikTrip #1496
T11CM00396, T11CM00397 & T11BU00170
Building Plan (1st Review)

TRANSMITTAL DATE: February 28, 2011


1. The building, canopy and fuel tank plans have been reviewed by Zoning Review Section but cannot approve the plans until all zoning comments or concerns have been addressed.

2. Zoning can not approve the plans until the development package has been approved.

3. Zoning will re-review the plans on the next submittal to insure compliance with the approved and development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\building\t11cm00396.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

Final Status

Task End Date Reviewer's Name Type of Review Description
05/02/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
05/02/2011 SUE REEVES REJECT SHELF Completed