Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00391
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 02/03/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 02/03/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 02/03/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/04/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 02/04/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise fonts to a minimum height of 3/32". 2. Show the trap and vent for the floor sink; show the vent and drain sizes. 3. Specify the floor sink to be used (e.g. size, material, standards). 4. Provide backflow protection for the BIC machine. 5. Clarify the additional keynote #4. 6. Show the revisions to the drain and vent piping for the relocated hand sink. |
| 02/04/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/04/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/04/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/08/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/08/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |