Permit Number: T11CM00390
Parcel: 105102440

Address:
495 E WETMORE RD

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T11CM00390
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2011 MARTIN BROWN FIRE REVIEW Approved
03/04/2011 GERRY KOZIOL WWM REVIEW Approved
03/07/2011 PAUL MACHADO ENGINEERING REVIEW Approved
03/10/2011 TERRY STEVENS ZONING REVIEW Approved
03/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Existing building background on all floor plans are drafted too light. Please increase the line weight for the existinmg conditions for all floor plans and resubmit.
03/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide complete plumbing plans for the new work, including waste and vent isometrics of the new work. Reference: Section 103.2.3, UPC 2006.
03/23/2011 ROBERT SHERRY WATER REVIEW Approved
03/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM00390
495 E Wetmore

Electrical plans denied for the following:

1. Al lettering and numbering to br min 3/32".
2. Date Load calculation Report.
3. Existing panel too light.
4. Identify circuits for power and lighting, show panel location.

Ray T Majuta,
Elect Pln Ck,
PDSD, City of Tucson
3/28/11,
Ray.majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/28/2011 SUE REEVES REJECT SHELF RECEIVED