Permit Number: T11CM00388
Parcel: 13613001W

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T11CM00388
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2011 TERRY STEVENS ZONING REVIEW Approved
02/03/2011 ANY WWM REVIEW Active
02/03/2011 RONALD BROWN ADA REVIEW Passed
02/03/2011 JASON GREEN ENGINEERING REVIEW Approved
02/03/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved Comments addressed by registrant's employee over the counter.
1. Revise fonts to a minimum height of 3/32".
2. Show the trap and vent for the floor sink; show the vent and drain sizes.
3. Specify the floor sink to be used (e.g. size, material, standards).
4. Provide backflow protection for the BIC machine.
02/04/2011 ROBERT SHERRY WATER REVIEW Approved
02/04/2011 MARTIN BROWN FIRE REVIEW Approved
02/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved