Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM00385
Parcel: 13316021D

Address:
6616 E GRANT RD

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T11CM00385
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2011 TERRY STEVENS ZONING REVIEW Approved
02/03/2011 ANY WWM REVIEW Active
02/03/2011 RONALD BROWN ADA REVIEW Passed
02/03/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
02/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/04/2011 ROBERT SHERRY WATER REVIEW Approved
02/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved Comments addressed by registrant's employee over the counter.
1. Revise fonts to a minimum height of 3/32".
2. Show the trap and vent for the floor sink; show the vent and drain sizes.
3. Specify the floor sink to be used (e.g. size, material, standards).
4. Provide backflow protection for the BIC machine.
02/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/04/2011 MARTIN BROWN FIRE REVIEW Approved
02/04/2011 PAUL MACHADO ENGINEERING REVIEW Approved
02/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved