Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM00382
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00382
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2011 STEVE SHIELDS ZONING REVIEW Approved
02/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/03/2011 ROBERT SHERRY WATER REVIEW Approved
02/03/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.1; PLAN KEYNOTES: NOTE 14 REFERENCES A WALL SCHEDULE. PROVIDE.
02/03/2011 BEV HESTER ENGINEERING REVIEW Approved
02/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the mechanical/plumbing design with the architectural sheets (i.e. show the stacked washer/dryer)
2. Provide an expansion tank for the water heater.
02/03/2011 DAVE MANN FIRE REVIEW Approved
02/03/2011 ERIC NEWCOMB ADA REVIEW Passed
02/03/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/07/2011 GBONILL1 WWM REVIEW Needs Review