Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00380
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/03/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
02/07/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The kitchen equipment drawing calls for a water connection to a chemical dispensing system at the mop sink (P4) and at the 3-compartment sink (32). Show these connections on the riser diagram and indicate the type of backflow preventer required, if any. Reference: Sections 103.2.3 and 603.0, UPC 2006. 2. A restaurant is assembly occupancy; revise the water and waste water fixture units as needed. Reference: Sections 610.1 and 702.0, UPC 2006. 3. A combination waste and vent system is not approved for use in a grease waste system. Reference: Sections 910.1 and 910.2, UPC 2006. 4. Coordinate the gas piping size and developed length as shown on detail 1/P3 with the plumbing plan on sheet P2. Reference: Section 103.2.3, UPC 2006 |
02/07/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/08/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Ventilation for restrooms in public spaces based on the use of ASHRAE 62.1-2004 requires a minimum of 70 CFM of mechanical exhaust per water closet or urinal "where periods of heavy use are expected to occur". Reference: Table 6-4, footnote D, ASHRAE 62.1-2004. 2. Show that the clearances for the grease duct comply with Section 506.3.6, IMC 2006 (i.e. the wall construction noted as "B" does not specify that no combustible support materials are to be within 18" of the hood). |
02/15/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/16/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
02/16/2011 | SUE REEVES | REJECT SHELF | Completed |