Permit Number: T11CM00370
Parcel: 131090060

Address:
5802 E 22ND ST

Review Status: Completed

Review Details: SITE

Permit Number - T11CM00370
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2011 RONALD BROWN ADA REVIEW Passed
02/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the location and size of the water meter
b. the location of the main water lines and fire hydrants
c. the location and size of the public sanitary sewer
d. the location of the building connection to the public sewer
e. the location, invert, and rim elevation of all manholes and cleanouts
f. the first floor elevation for the building
Reference: City of Tucson Development Standard No. 2-05.0, Section 2.3 D and Section 103.2.3, UPC 2006.
03/07/2011 RONALD BROWN H/C SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/07/2011 CINDY AGUILAR OUT TO CUSTOMER Completed