Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM00370
Parcel: 131090060

Address:
5802 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00370
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2011 STEVE SHIELDS ZONING REVIEW Approved
02/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/17/2011 GERRY KOZIOL WWM REVIEW Approved
02/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the pipe sizes for the wet vent for floor sink, E-1, and the hand sink, 21. Reference: Sections 103.2.3 and 908.2, UPC 2006
2. Complete the labeling of the pipes (including the existing drain pipes) shown on detail A/P1. Reference: Section 103.2.3, UPC 2006.
3. Coordinate detail 110/M3 with the flue called out on sheet M1. Reference: Section 103.2.3, UPC 2006.
4. Correct the fixture units for the water closets for assembly occupancy. Reference: Tables 6-5 and 7-3, UPC 2006.
02/25/2011 ROBERT SHERRY WATER REVIEW Approved
02/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the occupancy of the customer area to "cafeteria/fast food dining" rather than "dining". Reference: Table 6-1, ASHRAE Standard 62.1-2004.
2. Coordinate the structural detail, 118/S1.3, with Section 507.6, IMC 2006 to include the "possible weight of personnel working on or in the hood".
3. Include EF-5 in the air balance schedule on sheet M2. Reference: Section 508.0, IMC 2006.
03/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved