Permit Number: T11CM00357
Parcel: 14043011A

Address:
7001 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00357
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/02/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The revised waste and vent isometric (C) now shows the existing conditions and the proposed condition but the two isometrics appear to show the existing 3" building drain (running from the wet-vented P-3 and P-2A fixtures to the third P-2A) becoming an "existing" 4" building drain; clarify. [Original Comment: Provide cleanouts sized per Section 707.11, UPC 2006 (see detail C/P3, 4"S at connection of P-4).]
06/10/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2011 CPIERCE1 OUT TO CUSTOMER Completed
06/13/2011 SUE REEVES REJECT SHELF Completed