Permit Number: T11CM00357
Parcel: 14043011A

Address:
7001 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00357
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2011 DAVE MANN FIRE REVIEW Approved
02/07/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T11CM00357
TI Office and Warehouse
Ascent Aviation Services

Electrical denied for the following:

1. All new wiring and new fixtures on Sheet E-2 shall be circuited and identified with their panel.
2. Sheet E-3, circuits 1L1-20,22,24 shown as spares, are listed on power plan as circuits for furniture, label as such and provide load in panel, or omit in plan.
3. New panels are to have fault current they need to be rated for on panel schedule.

Ray Majuta
Elect Pln Ck,PDSD
City of Tucson,
2/8/11
Ray.Majuta@tucsonaz.gov
02/09/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide last approved site plan.
2. Please provide the additional information on your code review checklist:
a. Total Occupancy Load
b. Please provide a complete list of hazardous materials intended to be stored and their quantities.
3. Please provide the additional information for room numbers 125, 126 and 127:
a. Please further explain their use
b. Please provide a list of hazardous materials to be stored and their quantities.
3. Please list the accessibility construction item changes and provide a calculation of their overall cost and percentage of the overall construction budget.
4. Please provide a battery storage summary. Provide the types and quantities of batteries and any hazardous battery support material and their quantities.
END OF REVIEW
02/15/2011 GERRY KOZIOL WWM REVIEW Approved
02/28/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanouts sized per Section 707.11, UPC 2006 (see detail C/P3, 4"S at connection of P-4).
2. The size of a wet vent shall be a minimum of one pipe size greater than that required for the drain of the upper fixture (see detail C/P3, fixtures P-2A and P-3). Reference: Section 908.2, UPC 2006.
02/28/2011 ROBERT SHERRY WATER REVIEW Approved
02/28/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2 (installed). Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
2. Provide manufacturer's listing and equipment data along with mechanical and electrical operating information for the Airwall 60LD dust collector. Reference: Section 301.6, IMC 2006.
3. Provide manufacturer's listing and equipment data along with mechanical, electrical, and chemical use information for the relocated spray booth. Reference: Section 301.6, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2011 DELMA ROBEY OUT TO CUSTOMER Completed
03/09/2011 SUE REEVES REJECT SHELF Completed