Permit Number: T11CM00352
Parcel: 112032600

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM00352
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2011 GERRY KOZIOL WWM REVIEW Approved
03/15/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-16-11
Activity: T11CM00352
Address: 3221 N Christmas Ave
Applicant: Benjamin Design

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Any architect and/or engineer involved in the design of the structure shall seal the related new or revised sheets of plans including details and calculations in accordance with the rules of the State Board of Technical Registration.

FOUNDATION PLAN:
2. Designate footing types on foundation layout according to footing schedule.

STRUCTURAL / FRAMING PLAN:
3. Clarify how garage roof is to remain unchanged if supporting walls are extended to match wall heights of existing house.

PLUMBING PLAN:
4. Provide minimum 1½" gas supply line from gas meter for proposed demand.
5. Provide minimum 1¼" gas line past range for proposed demand.
6. Provide plumbing fixture unit values consistent with the 2006 IRC.

ELECTRICAL PLAN:
7. Clarify entertainment center circuit serving outdoor receptacles.
8. Include garage circuits on subpanel 'B' load calculation.
9. 40% load reduction is not allowed for subpanels.
10. Provide riser diagram for proposed installation.
11. Correct note references to the 2000 IRC.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review