Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM00331
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/09/2011 | RONALD BROWN | ADA | REVIEW | Passed | Reference building comments |
| 02/10/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 02/15/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEETS 2A0.1 AND 2A2.1: 1. The most Southerly marked crossing from the business office island to the most Easterly island median is not as per the approved Development Plans, sheet C6, D08-0055. Please revise drawings and resubmit. 2. The special inspections certifications are not included with this submittal as required and summarized on sheet 2S1.3. 3. Please provide a letter of deferred submittals to the Building Official, Mr. Ron Boose for additional plan review assessment. END OF REVIEW |
| 02/17/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER NEED TO PERMIT ON-SITE PRIVATE SEWER NEED DEQ REVIEW & APPROVAL TO CONSTRUCT ON-SITE PRIVATE NEED COPY OF APPROVED ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE |
| 02/25/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T11CM00331, 5300 E Los Reales Scale House Electrical Plans denied for the following: 1. 2E1.2, Key Note 5, indicates the 1400 A SES is new, sheet 2E3.1 appears to indicate SES is existing. 2. 2E3.1, the feeder from the SES to the new Transfer Switch and Generator is in a dotted line form indicating it is existing, please show all new work in bold lines and indicate as new, in order to differ from existing. 3. What is the location of the SES, and indicate on the one line diagram. 4. Provide a total load summary for the existing plus the new loads. Ray T Majuta, Elect Pln Ck, PDSD, City of Tucson, 2/26/11, Ray.Majuta@tucsonaz.gov |
| 02/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The site plan, sheet 2A0.1, shows an 8" building sewer with five manholes. The presence of manholes in a private sewer collection system will require review of the sewer design by the Pima County Department of Environmental Quality. A separate plumbing permit from Development Services will be required for construction of the private sewer collection system. 2. Provide specifications for all of the proposed pipe and plumbing materials (e.g. water, waste, vent, and 2-way cleanout). Reference: Sections 303.4, 605, 702, and 708.3.5, IPC 2006. 3. Provide information to show how the proposed water heater platform is to be connected to the building structure. Reference: Section 307.1, IPC 2006. 4. Clearly show the location of the plumbing vent that terminates through the building wall. Reference: Section 904.6, IPC 2006. |
| 02/28/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Keynote #3 on sheet 2M1.1 calls for the condensate drain piping to be routed as shown on the plumbing drawings but no condensate piping is shown on the plumbing drawing. Show the size, route, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2006 as amended by the City of Tucson. |
| 03/08/2011 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | As stated previously, a grading permit is required for this project. When ready, provide 2 sets of civil/grading plan sheets with SWPPP, a grading permit application, and a floodplain use permit application. Clarify extents of improvements on plans including all areas for Phase 1. Grading permit is required to be issued prior to or concurrently with this building permit. |
| 03/09/2011 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/14/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 03/14/2011 | SUE REEVES | REJECT SHELF | Completed |