Permit Number: T11CM00329
Parcel: 121016460

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00329
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2011 PAUL MACHADO ENGINEERING REVIEW Denied The project has denied and will not be reviewed until a FUP has been submitted. PM. 02-01-11.
02/03/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T11CM00329

Electrical denied for the following:

1. Calculated load shows 1004 amps, the SES has a Main Breaker of 600 amps.
2. The existing meters are marked spares, actually being used ?

Ray T Majuta,
Elect Pln CK, PDSD, City of Tuc,
2/4/11
520-837-4988