Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00283
Parcel: 138142920

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00283
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-1-11
Activity: T11CM00283
Address: 274 W Hatfield St
Applicant: Earl Kai Chann

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Any architect and/or engineer involved in the design of the structure shall seal the related new or revised sheets of plans including details and calculations in accordance with the rules of the State Board of Technical Registration.
2. Provide sufficient emergency escape/rescue openings from sleeping rooms with a maximum sill height of 44 inches above finished floor elevation, R310.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2011 SUE REEVES OUT TO CUSTOMER Completed
03/04/2011 SUE REEVES REJECT SHELF Completed