Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
01/28/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/28/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
01/28/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/28/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/28/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
01/28/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
01/28/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
01/28/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/31/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Electrical denied, 1. Evap coolers require 120 volt for pump ? 2. Maintenance receptacle required for unit on roof,2005 NEC 210.63. 3 Sheet E1.0 is too light on power plan and General Notes. Ray Majuta PDSD, City of Tucson, Elect Pln Ck 1/31/11 |
01/31/2011 | DAVE MANN | FIRE | REVIEW | Approved |