Permit Number: T11CM00247
Parcel: 129021020

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00247
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 4-13-11
Activity: T11CM00247
Address: 257 S Eastbourne Av
Applicant: Dan Gullick

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Correct mislabeled cross references to section details on sheet 5.
2. Specify the location for detail 8 on framing layout.
3. Provide construction drawings for garage.

STRUCTURAL / FRAMING PLAN:
4. Specify length of rafter scabs at front overhang and connection to existing structure.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/18/2011 DELMA ROBEY OUT TO CUSTOMER Completed