Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00221
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/26/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
01/26/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the ductwork is to be modified. |
01/26/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/26/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/26/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/26/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
01/26/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
01/26/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
01/26/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
01/26/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
01/26/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |