Review Details: COMMERCIAL - TI

Permit Number - T11CM00203
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2011 TERRY STEVENS ZONING REVIEW Approved
01/25/2011 JASON GREEN ENGINEERING REVIEW Approved
01/26/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/26/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/26/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/26/2011 ROBERT SHERRY WATER REVIEW Approved .
01/26/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the size of the water meter; it is shown as an existing 5/8" meter on sheet P-1 but the water calculations on sheet P-1 indicate a 1" water meter.
2. The "optional" elelctric water cooler does not meet the accessibility requirements of Section 1109.5, IBC 2006.
3. A point-of-use water dispenser does not have a drain; modify the waste and vent riser as needed.
4. If a point-of-use water dispenser is to be installed, it must be installed prior to the plumbing final inspection.
01/26/2011 DAVE MANN FIRE REVIEW Denied Additional exit signs required from storage areas into office
01/26/2011 ERIC NEWCOMB ADA REVIEW Passed
01/26/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
02/02/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/02/2011 DELMA ROBEY OUT TO CUSTOMER Completed