Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00203
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/25/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 01/25/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/26/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/26/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/26/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/26/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | . |
| 01/26/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the size of the water meter; it is shown as an existing 5/8" meter on sheet P-1 but the water calculations on sheet P-1 indicate a 1" water meter. 2. The "optional" elelctric water cooler does not meet the accessibility requirements of Section 1109.5, IBC 2006. 3. A point-of-use water dispenser does not have a drain; modify the waste and vent riser as needed. 4. If a point-of-use water dispenser is to be installed, it must be installed prior to the plumbing final inspection. |
| 01/26/2011 | DAVE MANN | FIRE | REVIEW | Denied | Additional exit signs required from storage areas into office |
| 01/26/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/26/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 02/02/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/02/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |