Permit Number: T11CM00202
Parcel: 123130600

Address:
2136 N EUCLID AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM00202
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2011 GERRY KOZIOL WWM REVIEW Approved
02/14/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-14-11
Activity: T11CM00202
Address: 2136 N Euclid Ave
Applicant: Rhonda Rawson

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Any architect and/or engineer involved in the design of the structure shall seal the related new or revised sheets of plans including details and calculations in accordance with the rules of the State Board of Technical Registration.
2. Taped on modifications are not allowed on original drawings. Provide copies of cover sheet.
3. Correct all mislabeled section references.
4. Clarify all overtyping.

SITE PLAN:
5. Location of electric service panel on site plan does not match location on electrical plan.

FOUNDATION PLAN:
6. Show locations of all embedded hardware on foundation plan.
7. Specify sizes of all point-load footings, R401.2.
8. Show no-step entry for Inclusive Home Design ordinance.

STRUCTURAL / FRAMING PLAN:
9. Clarify shearwall note 2 on sheet A-1a.
10. Show lateral load transfer from second floor, R602.10.8.
11. Provide interior braced wall lines max 35'o.c, R602.10.1.1, R602.10.8.
12. Designate locations of second floor braced wall panels, R602.10.1.1, R602.10.8.
13. Clarify locations of metal strapping between floors.
14. Designate all interior load bearing walls on framing plan.

SECTIONS - DETAILS:
15. Clarify interior load bearing walls and supporting footings on cross section.
16. Provide all missing section details.
17. Specify weep screed condition at exterior slabs when even with finished floor elevation, R703.6.2.1.
18. Clarify anti-rotation support detail 2 sheet D-2,R502.7.

PLUMBING PLAN:
19. Correct pressure loss calculation for elevation change on water supply schedule, P2903.7.1(1.1).

MECHANICAL PLAN:
20. Show dryer vent size and location for venting to exterior (max 25' w/bend reductions), M1502.2, M1502.6.
21. Clarify location of supply and return air ducts, M1403.1.
22. Specify kitchen exhaust venting to the exterior minimum 100 CFM, R303.3, M1507.

ELECTRICAL PLAN:
23. Show receptacle outlets at each kitchen counter space wider than 12" so that no point along the wall line is more than 24" from a receptacle outlet, E3801.4.1.
24. Designate the circuit number for each light fixture, receptacle, appliance, and equip disconnect on the electrical layout, E3603.5.
25. Clarify location of subpanel B.
26. Specify the grounding electrode method, E3508.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2011 DELMA ROBEY OUT TO CUSTOMER Completed