Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00201
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/26/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/26/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 01/27/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/27/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Generic accessibility details are not acceptable. Please actual toilet plan and elevations with all accessible requirements show on these details including dimensions. |
| 01/27/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 01/27/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/28/2011 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/28/2011 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 01/28/2011 | CPIERCE1 | WATER | REVIEW | Needs Review | |
| 01/28/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |