Permit Number: T11CM00189
Parcel: 12510003F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00189
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2011 TERRY STEVENS ZONING REVIEW Approved
01/24/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the proposed revisions to the projector exhaust ducts.
01/24/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/24/2011 ROBERT SHERRY WATER REVIEW Approved
01/24/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. COVER SHEET; SCOPE OF WORK: IS THIS AUDITORIUM #10? REVISE.
2. COVER SHEET: GIVE SQUARE FOOTAGE AND OCCUPANT LOAD FOR AUDITORIUM #10.
3. COVER SHEET: DO THE HANDRAIL HEIGHTS MEET THE REQUIREMENTS OF SECTION 1012 IN THE 2006 IBC? VERIFY.
4. SHEET A3: ARE THE GUARDRAILS REQUIRED PER SECTION 1013 IN THE 2006 IBC? VERIFY.
5. SHEET A5; DETAIL 8: CHECK THE HEIGHT OF THE LOW WALL. DOES THIS MEET THE REQUIREMENTS OF SECTION 1013 IN THE 2006 IBC? VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/24/2011 PAUL MACHADO ENGINEERING REVIEW Approved
01/24/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the 2" waste line from above the mezzanine - i.e. what is connected to it?
01/24/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/24/2011 ERIC NEWCOMB ADA REVIEW Passed
01/27/2011 GERRY KOZIOL WWM REVIEW Approved
01/27/2011 MARTIN BROWN FIRE REVIEW Approved