Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00175
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/21/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/21/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00175 7700 E Wrightstown, 1. Sheet E-1, circuit A-6 cannot be used for lighting since it is already used for one leg of an AC circuit. 2. Sheet E-4, the #2 cu grd for the service should be 2/0 cu per 2005 NEC 250.66. 3. The supply side of the 400 amp main disconnect feed should have a 1/0 cu grd per 250.66 since it's on the supply side it is sized per 250.66 Ray Majuta' PDSD, City of Tucson, 1/21/11 |
| 01/21/2011 | LHANLY1 | WATER | REVIEW | Approved | |
| 01/21/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE HIGH/LOW OR SINGLE POINT-OF-USE DRINKING FOUNTAIN AS REQUIRED BY 2006 IBC. 2. PROVIDE STRUCTURAL ANALYSIS OF NEW AC UNIT LOADS ON EXISTING ROOF STRUCTURE, INDICATING THAT EXISTING STRUCTURE CAN ADEQUATELY RESIST NEW LOADS. |
| 01/21/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/21/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Need exit sign over second exit door |
| 01/21/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/21/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/26/2011 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 01/26/2011 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |