Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00164
Parcel: 123110260

Address:
1028 E LESTER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM00164
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2011 GERRY KOZIOL WWM REVIEW Approved
02/04/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-07-11
Activity: T11CM00164
Address: 1028 E Lester St
Applicant: Isaac Armenta

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Correct mislabeled reference to sheet 8 on braced wall description on sheet 3.

PLUMBING PLAN:
2. Show two-way cleanouts within 2' from the, P3005.2.
3. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.

ELECTRICAL PLAN:
4. Kitchen lights may not share the small appliance circuits, E3801.3.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2011 DELMA ROBEY OUT TO CUSTOMER Completed