Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM00154
Parcel: 136090300

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T11CM00154
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2011 SEPTIC APPROVAL WWM REVIEW Denied need PC septic review. Septic undersized
02/02/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-4-11
Activity: T11CM00154
Address: 11001 E Old Spanish Tr.
Applicant: Rick Young

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Provide a water fixture unit schedule for the entire property (including existing) P2903.6.
2. Provide the maximum developed length of water line from the meter the furthest appliance served, the lowest available pressure, and the diameter of the water service line, P2903.7.

ELECTRICAL PLAN:
3. Bathrooms require a separate 20-amp circuit, E3603.4, E3801.6.
4. Correct mislabeled circuit references for water heater and dryer.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/11/2011 SUE REEVES REJECT SHELF Completed