Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM00151
Parcel: 11205061A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00151
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2011 PAUL MACHADO ENGINEERING REVIEW Approved
02/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET AS-101
1. Please provide an accessible route from the new accessible parking space to the Hedrick public right of way as per 2006 IBC, Section 1104.1.
2. The marked crossing is non-compliant.
a. The 90 degree corner turn is an accessible route located in a hazardous location in the PAAL susceptible to auto back up and roll over. Please redesign your marked crossing for a direct connection to the concrete accessible route in front of the building.
c. The marked crossing must have detectable warnings at both ends as per 2006 IBC, ICC (ANSI 1171.), Section 404.12 and 404.13.
3. The one accessible parking space must be "Van Accessible" as per 2006 IBC, Section 1106.5 and ICC (ANSI 117.1), Section 502. Reference the required width options available.
4. Show location of the accessible parking signage on the site plan and detail. Please show a large scale signage detail.
5. Please show accessible route slope compliance with ICC (ANSI 117.1), Section 403.3.
SHEET A-102
6. Please provide accessible drinking fountain as per 2006 IBC, Section 1109.5 and ICC (ANSI 117.1), Section 602.
7. Door 204-2 may not swing into the required toilet and lavatory clear spaces as per ICC (ANSI 117.1), Section 603.2.3.
SHEET A-202
8. Detail A3/ADA CLEARANCES: ADA is not the governing accessible standards to be used with the 2006 IBC. Chapter 11, Section 1101.2 states that all accessible requirements are to be as per ICC (ANSI 117.1, 2003 Edition). Please note this code reference on the drawings.
9. Generic accessible details copied from the code book are not acceptable. Please show all accessible requirements on the actual design, large scale toilet plans and interior elevations.
SHEET S-101
10. At detail C5, please include the plate to column welding requirements as shown on the calculations, page 1.
END OF REVIEW

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2011 DELMA ROBEY OUT TO CUSTOMER Completed