Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00139
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
01/18/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
01/19/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
01/19/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a mechanical plan that includes specifications and balancing data for the exhaust fans. |
01/19/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE DETAILS/SECTIONS OF HOW THE NEW INTERIOR PARTITIONS MEET THE LATERAL LOAD REQUIREMENTS OF THE IBC SECTION 1607.13. |
01/19/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 101.5.1, UPC 2006. |
01/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics, fixture, fitting, and equipment specifications, and water pressure calculations. Reference: Section 103.2.3, UPC 2006. |
01/19/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
01/19/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/28/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
02/28/2011 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |