Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM00139
Parcel: 13216639A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00139
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2011 TERRY STEVENS ZONING REVIEW Approved
01/18/2011 PAUL MACHADO ENGINEERING REVIEW Approved
01/19/2011 ERIC NEWCOMB ADA REVIEW Passed
01/19/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a mechanical plan that includes specifications and balancing data for the exhaust fans.
01/19/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DETAILS/SECTIONS OF HOW THE NEW INTERIOR PARTITIONS MEET THE LATERAL LOAD REQUIREMENTS OF THE IBC SECTION 1607.13.
01/19/2011 ROBERT SHERRY WATER REVIEW Denied Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 101.5.1, UPC 2006.
01/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics, fixture, fitting, and equipment specifications, and water pressure calculations. Reference: Section 103.2.3, UPC 2006.
01/19/2011 DAVE MANN FIRE REVIEW Approved
01/19/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/28/2011 CPIERCE1 WWM REVIEW Needs Review
02/28/2011 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review