01/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum slope for drain pipes smaller than 4" is 1/4" per 12". Reference: Section 718.1, UPC 2006.
2. Provide a vent for the sand-oil separator. Reference: Section 1009.4, UPC 2006.
3. A 2-way cleanout is approved only at the junction of a building drain and a building sewer. Reference: Section 707.4, UPC 2006.
4. A slope of 1/8" per 12" is allowed only where it is impractical to use a slope of 1/4" per 12". Reference: section 6718.1, UPC 2006.
5. The maximum distance between cleanouts shall be 100 feet. reference: section 719.1, UPC 2006.