Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/18/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum slope for drain pipes smaller than 4" is 1/4" per 12". Reference: Section 718.1, UPC 2006. 2. Provide a vent for the sand-oil separator. Reference: Section 1009.4, UPC 2006. 3. A 2-way cleanout is approved only at the junction of a building drain and a building sewer. Reference: Section 707.4, UPC 2006. 4. A slope of 1/8" per 12" is allowed only where it is impractical to use a slope of 1/4" per 12". Reference: section 6718.1, UPC 2006. 5. The maximum distance between cleanouts shall be 100 feet. reference: section 719.1, UPC 2006. |
01/21/2011 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
01/21/2011 | DROBEY1 | ZONING | REVIEW | Needs Review | |
01/21/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/21/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |