Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM00126
Parcel: 10408078C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM00126
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum slope for drain pipes smaller than 4" is 1/4" per 12". Reference: Section 718.1, UPC 2006.
2. Provide a vent for the sand-oil separator. Reference: Section 1009.4, UPC 2006.
3. A 2-way cleanout is approved only at the junction of a building drain and a building sewer. Reference: Section 707.4, UPC 2006.
4. A slope of 1/8" per 12" is allowed only where it is impractical to use a slope of 1/4" per 12". Reference: section 6718.1, UPC 2006.
5. The maximum distance between cleanouts shall be 100 feet. reference: section 719.1, UPC 2006.
01/21/2011 DROBEY1 ENGINEERING REVIEW Needs Review
01/21/2011 DROBEY1 ZONING REVIEW Needs Review
01/21/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2011 DELMA ROBEY OUT TO CUSTOMER Completed