Permit Number: T11CM00125
Parcel: 10705146A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM00125
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project T11CM00125
870 W Miracle Mile
Photovoltaic System

Electrical plans denied for the following,

The use of Polaris connectors for line side taps on conductors in existing disconnects means is prohibited in this Jurisdiction. The conductors for the PV system are required to land on individual terminals listed and approved for their use.

Ray T Majuta,
Elect Plan Ck,
PDSD, City of Tucson,
1/31/11,
Ray.Majuta@tucsonaz.gov
02/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. DRAWING NUMBER 2011004; PLAN: PER THE 2006 IBC, SECTION 106.1.1, DIMENSIONALLY LOCATE ALL PHOTOVOLTAIC ARRAYS ON THE PLAN.
2. DRAWING NUMBER 2011004; TJI CAPACITY CALCULATION: THE CALCULATION EXAMPLE DOES NOT INCLUDE THE 20 PSF LIVE LOAD AS REQUIRED BY THE 2006 IBC, TABLE 1607.1. REVISE.
3. DRAWING NUMBER 2011005: ON THIS SHEET, LIST THE WIND SPEED (3 SECOND GUST) AND THE EXPOSURE CATEGORY USED FOR THE ANALYSIS.
4. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/17/2011 CPIERCE1 OUT TO CUSTOMER Completed
02/17/2011 SUE REEVES REJECT SHELF Completed