Review Details: REVISION - - 3RD

Permit Number - T11CM00119
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE REMOVE REFERENCES TO WHAT WAS EXISTING ON PP A3.1...IF YOU ARE REPLACING IT THEN WE DON'T NEED TO KNOW WHAT WAS THERE BEFORE. KEEP "EXISTING" INFORMATION ONLY FOR THAT EQUIPMENT OR CIRCUITRY YOU ARE NOT MOVING OR REPLACING.

HOW ARE YOU PROVIDING POWER TO PNL B? THERE IS NO REFERENCE FROM PNL A

PROVIDE LOAD CALCULATIONS FOR ALL PANELS

PROVIDE AN AVAILABLE GROUND FAULT ANALYSIS TO JUSTIFY AIC RATING OF PANELS

ALL PLANS MUST BE SEALED BY AN ARIZONA REGISTRANT.