Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/23/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLEASE REMOVE REFERENCES TO WHAT WAS EXISTING ON PP A3.1...IF YOU ARE REPLACING IT THEN WE DON'T NEED TO KNOW WHAT WAS THERE BEFORE. KEEP "EXISTING" INFORMATION ONLY FOR THAT EQUIPMENT OR CIRCUITRY YOU ARE NOT MOVING OR REPLACING. HOW ARE YOU PROVIDING POWER TO PNL B? THERE IS NO REFERENCE FROM PNL A PROVIDE LOAD CALCULATIONS FOR ALL PANELS PROVIDE AN AVAILABLE GROUND FAULT ANALYSIS TO JUSTIFY AIC RATING OF PANELS ALL PLANS MUST BE SEALED BY AN ARIZONA REGISTRANT. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/24/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
06/24/2011 | SUE REEVES | REJECT SHELF | Completed |