03/31/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
Show corrections and revisions on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and notate sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

GENERAL NOTES:

" Provide legible notation (minimum 3/32" lettering). Clarify undersized lettering at Details and Keynote #1 on sheet #3.0.
" Provide consecutive sheet numbers on each construction drawing, R106.1.1. Provide two copies of sheet #2 with sheet number clarification.

SITE PLAN:

1. Clarify the existing and proposed gas meter location, R106.1.1.

FOUNDATION PLANS:

1. Show a minimum 12" x 12" footing depth below undisturbed soil for new framed exterior walls of enclosed roof structures, with minimum of one #4 reinforcement rebar, R403.1. (City of Tucson Amended).
2. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with (anchor bolt length for assuring) 7" embedment into concrete or masonry, R319.1 & R403.1.6. Maximum spacing 6' o/c and within 12" of each sill plate end, R403.1.6.

STRUCTURAL PLANS:

1. Show beam sizes with appropriate load carrying capacity, R301.1. The longer two B-1 beams are under sized for a roof structure with ceiling.
2. Clarify the existing block wall width and height. Provide the structural plans if over 6' high. Provide a registered Arizona engineer's design if the height of the existing wall be being extended, R301.1.
3. Show existing bond beam for connecting the roof structure shown on Detail 6 sheet 3.0, or provide a registered Arizona engineer's design if altering the wall, Table R606.9.
4. Show the ledger bolt size and spacing in compliance with Figure R606.11 (1).
5. Notate the requirement for ledger anchorage where rafters are parallel to wall, ½" bolts at 8' O.C. with 4" embedment, R606.11.

ELEVATIONS:

1. Clarify the height of existing block wall (keynote #4 sheet 3.0. Permit T99BU00306 provided 100 lf of 6 foot wall, R301.1.
2. Roof shingles may be used on roof slopes of 2:12 or greater R905.2.2. Select a roof system that complies with R905.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground, R319.1 item 5.
2. Specify all ledgers connected to masonry walls with 3x material (Rear Elevation wall), R606.11.

PLUMBING PLANS:

1. Provide gas pipe sizes in compliance with connected demand as a result of the relocated gas mete, G2413.3 & Table G2413.4(1).

If you have any questions please contact:
Ken Van Karsen