Permit Number: T11CM00114
Parcel: 136100700

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00114
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T11CM00114
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:

" Provide manufacturer specification sheets for the mounting hardware.

STRUCTURAL PLANS:

1. Provide an engineer's calculation, design and seal for verifying the load carrying capacity of the non-prescriptive cantilever panel layout, M1401. Include appropriate mounting rail and uplift calculations.
2. Provide complete roof framing information for determining load carrying capacity of the porch roof, R301.1. Show the rafter attachment to the dwelling. The layout plan (sheet #2) shows attachment at the dwelling roof edge rather than a typically backset exterior wall.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
01/19/2011 SUE REEVES REJECT SHELF Completed