Permit Number: T11CM00103
Parcel: 12201024J

Address:
3920 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00103
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/23/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The submitted manufacturer's literature does not include any listing information for the power exhauster nor does it include the necessary balancing information for a power exhauster. The key note on sheet M1.1 does not indicate the presence of a power exhauster and similarly, the electrical power plans do not show any power for an exhaust fan for the utensil washer. [Provide listing information for the power exhauster for the utensil washer (detail HSD-8).]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2011 SUE REEVES OUT TO CUSTOMER Completed
03/29/2011 SUE REEVES REJECT SHELF Completed