Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM00103
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/23/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/23/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. The submitted manufacturer's literature does not include any listing information for the power exhauster nor does it include the necessary balancing information for a power exhauster. The key note on sheet M1.1 does not indicate the presence of a power exhauster and similarly, the electrical power plans do not show any power for an exhaust fan for the utensil washer. [Provide listing information for the power exhauster for the utensil washer (detail HSD-8).] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 03/29/2011 | SUE REEVES | REJECT SHELF | Completed |