Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00103
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
01/21/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
01/24/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Generic details of copied code excerpts are not acceptable. Please show all accessible requirements and dimensions on the actually toilet interior elevations design.. 2. Minimum letting height for all lower and upper case fonts is 3/32". Several sheets do not meet this requirement and must be redawn and resubmitted: A5.2, A5.2.1, I1.1, a1.3, I1.1, several R and I sheets along with several plumbing and electrical sheets. 3. Several sheets did not print well and are very hard to read. These need to be reprinted and resubmitted: A5.2, A5.2.1 and several R sheets. END OF REVIEW. |
01/27/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
01/31/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/31/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch (upper and lower case). Reference: Section 106.1.1, IBC 2006. 2. Provide information to show that the proposed hub drain complies with Sections 411.1 and 804.1, UPC 2006. 3. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 4. Verify that an upper terminal cleanout will exist for the 4" sanitary drain being retained near column 1-A. Reference: Section 707.4, UPC 2006. 5. Each plumbing fixture (e.g. detail PSD-3/P5.2) shall be individually trapped except as allowed by Section 1001.2, UPC 2006. Reference: Section 1001.1, UPC 2006. 6. Floor drains for walk-in coolers shall comply with the requirements of Section 801.2.2, UPC 2006. 7. Section 1014.2.1, UPC 2006 requires a flow control be provided for each plumbing fixture that is connected to a hydromechanical grease interceptor and that each flow control device that is not integral to a hydromechanical grease interceptor shall be readily accessible and visible. The specified hydromechanical grease interceptor does not have an integral flow control device. 8. The air intake for a flow control device shall not terminate to the free atmosphere in the building. Reference: Section 1014.2.1, UPC 2006. |
02/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 3/32-inch (upper and lower case). Reference: Section 106.1.1, IBC 2006. 2. Revise the material used for the construction of the grease duct shown in detail HSD-7 to welded 16-gage steel or welded 18-gage stainless steel. Type B vent is not listed for use under negative pressure or as a grease duct. Reference: Section 506.3.1.1, IMC 2006. 3. Clarify the notes on sheet M1.1 that refer to a "rated roof-system", 1-1/2-hour fire/smoke dampers for the new rooftop unit ducts penetrating the rated roof system, and a shaft for one of the two new exhaust ducts in the bakery area. None of these items are shown on the Architectural drawings. 4. Provide listing information for the power exhauster for the utensil washer (detail HSD-8). 5. Provide listing information for the hood and exhaust fan supplied with the rack oven (detail HSD-7). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/08/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
03/08/2011 | SUE REEVES | REJECT SHELF | Completed |