Permit Number: T11CM00085
Parcel: 12702274B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM00085
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2011 JASON GREEN ENGINEERING REVIEW Approved
02/24/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At sheet T1.1, "Building Code Information", delete the reference to "Arizonians with Diasbilities Act" and reference the 2006 IBC, Chapter 11 and ICC (ANSI 117.1, 2003 Edition).
2. At sheet A1.5:
a. Please provide a note reference to the 2006 IBC, Chapter 11 and ICC (ANSI 117.1, 2003 Edition) for all accessibility requirements.
b. At detail nos. 1, 8 and 9 please relocate the toilet dispenser and provide a vertical grab bar as per the 2006 IBC, ICC (ANSI117.1, 2003 Edition), Section 604.5.1.
c. At detail nos. 1, 3 and 4, please provide a vertical grab bar as per the 2006 IBC, ICC (ANSI117.1, 2003 Edition), Section 604.5.1.
END OF REVIEW
03/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; correct the font size in detail 4/P3.1. [Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.]
2. Comment not resolved; detail 4/P3.1 still shows an incorrect pipe size. [Correct and coordinate details 3/P3.1 and 4/P3.1 with regard to the sizes of the gas piping. Reference: Sections 103.2.3 and 1217.1, UPC 2006.]
3. Comment not resolved. Show how and where the correctly-sized cleanouts are to be provided for the 4" drain lines in the cooking and prep areas. [Provide information to show that the cleanouts have been sized per Section 707.11, UPC 2006 (see the 4" drain lines in the cooking area and the prep area).]
03/02/2011 ROBERT SHERRY WATER REVIEW Approved
03/02/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; for a combined capacity of 24 tons of air conditioning, a 1-1/4" condensate drain is required. [Show the size, routing, and termination of the condensate drains from the new rooftop units. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.]
2. Comment not resolved. The occupant load used for calculating the minimum required ventilation for a fast food/cafeteria, based on Table 403.3, IMC 2006 is 100 persons per 1,000 square feet. Reference: Section 403.3, IMC 2006. [Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.]
3. Comment not resolved. With a flow rate of 1233 CFM, the 12" x 14" exhaust duct for KH-1 will have an air velocity of only 1056 feet per minute; far lower than the required minimum velocity of 1500 feet per minute. [Show the location of the grease exhaust duct for the griddle hood, KH-1, and indicate the size of the duct. Reference: Sections 106.3.1 and 506.3.4, IMC 2006, as amended by the City of Tucson.]
4. Comment not resolved. With a flow rate of 800 CFM, the 10" x 10" exhaust duct for KH-2 will have an air velocity of only 1152 feet per minute; far lower than the required minimum velocity of 1500 feet per minute. [Revise the size of the grease duct for the fryer hood, KH-2, to provide a minimum velocity of 1500 feet per minute (the mechanical floor plan shows a 14" x 12" duct and an exhaust flow rate of only 800 CFM). Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson.]
5. Comment not resolved. To comply with the requirements of Section 507.2.1.1, IMC 2006, the exhaust fan for the hood (and of course, the make-up air source) must start automatically with the commencement of cooking operations; the electrical schematic does not appear to provide that capability. [Provide information to show that the operation of the Type I hoods and the hood exhaust fans comply with Section 507.2.1.1, IMC 2006.]
03/04/2011 DAVID RIVERA ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/04/2011 DELMA ROBEY OUT TO CUSTOMER Completed
03/04/2011 DELMA ROBEY REJECT SHELF Completed