Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM00083
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/01/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise detail 4/M3.1 to coordinate with the design shown on M2.1. 2. Show how the fan coils are being connected to the building structure. Reference: Section 302.1, IMC 2006. 3. Provide auxiliary drain pans or secondary drain systems for fan coil units. Reference: Section 307.2.3 IMC 2006. 4. Revise the size of the common condensate drain in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. |
| 02/01/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM00038 1. The new M3.2 sheet shows the Air Handlers to have a 5KW heat system ? R T Majuta Elect Pln Ck 2/1/12 |
| 02/02/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/28/2012 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 02/28/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |