Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM00082
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/13/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 01/14/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/14/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/14/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0: THIS NEW TI IS FOR WORK IN VILLA 2. IT IS NOT CLEAR FROM THE TABLE ON THIS SHEET IF THE NEW OCCUPANCY LOAD IS INCLUDED IN THAT TABLE. PROVIDE THE DATA FOR THIS TI. CLARIFY. 2. SHEET A3.0; WALLS "A": PROVIDE VERTICAL GRAB BARS PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. 3. SHEET A4.0; DETAILS 8 AND 9: PROVIDE STRUCTURAL CALCULATIONS FOR THE STEEL LINTEL OVER THE OPENING. 4. SHEET A4.0; DETAIL 2: PROVIDE VERTICAL GRAB BARS. 5. SHEET A4.0; DETAIL 7: PROVIDE BRACING AT THE TOP OF THE NEW INTERIOR WALLS TO RESIST LATERAL LOADS PER IBC SECTION 1607.13. INCLUDE BRACING SIZE, SPACING, AND CONNECTION TO THE TOP OF THE WALL. INCLUDE BRACING DETAIL AT THE EXISTING FRAMING ABOVE. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/14/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/14/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide sufficient information to show that the installation of the new plumbing fixtures will not cause the existing water supply and sanitary waste systems to become overloaded. Reference: Section 101.5.1, UPC 2006. 2. The waste and vent schematic shows the new drainage piping connecting to an existing 4"building drain but plumbing floor plan shows an existing 3" building drain. What is the size of the existing building drain? 3. Clarify the nature of the "anti-scald" valve, i.e. to what standards is it made? Reference: Section 301.1.3, UPC 2006. |
| 01/14/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 01/14/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 01/14/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/21/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |