Permit Number: T11BU01685
Parcel: 13613001U

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T11BU01685
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2012 STEVE SHIELDS ZONING REVIEW Passed
12/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/21/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PUBLIC POOLS MUST COMPLY ANSI/NSPI-1.

PROVIDE 2 MEANS OF ACCESSIBLE ENTRY/EGRESS PER SECTION 23.1.7

STEPS DO NOT MEET DIMENSIONAL UNIFORMITY REQUIREMENTS...MAX 1/2" TOLERANCE ALLOWED FOR RISERS.

IF STEPS ARE GOING TO BE PART OF ACCESSIBLE ENTRY THEN THEY MUST COMPLY WITH ADAAG ACCESSIBLE STAIR REQUIREMENTS
12/21/2011 LOREN MAKUS ENGINEERING REVIEW Approved
12/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/21/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied NO ELECTRICAL PLANS PROVIDED. IF ELECTRICAL IS UNDER SEPARATE PERMIT THEN PLEASE INDICATE ON PLANS AND INCLUDE ACTIVITY #