Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11BU01577
Parcel: 12809016B

Address:
4701 E 22ND ST

Review Status: Completed

Review Details: TANKS

Permit Number - T11BU01577
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Provide cut sheets for the tanks, piping, and dispensers indicating the UL or other listing per IFC Section 2206.

Detail 5 on Sheet F3.2 must be corrected to show the bollards comply with IFC Section 312 for the four foot spacing all around the dispensers or provide a six inch high curb to protect the dispensers.
12/14/2011 TERRY STEVENS ZONING REVIEW Approved 10/27/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.
12/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved