Permit Review Detail
Review Status: Completed
Review Details: WALLS
Permit Number - T11BU01366
Review Name: WALLS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/18/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/18/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/18/2011 | ENEWCOM1 | NPPO | REVIEW | Passed | |
| 10/18/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; SECTION 5: PROVIDE THE FOOTING WIDTH AND DEPTH ON THE DRAWING PER THE STRUCTURAL CALCULATIONS. 2. SHEET A1.0; SECTION 5: NOTE 5 INDICATES A #4 CONTINUOUS IN SOLID GROUTED CELLS. THE BAR INDICATED IS IN THE FOUNDATION, NOT THE CMU. REVISE. |