Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T11BU01343
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Provide cut sheets for the tanks, piping, and dispensers indicating the UL or other listing per IFC Section 2206. Detail 5 on Sheet F3.2 must be corrected to show the bollards comply with IFC Section 312 for the four foot spacing all around the dispensers or provide a six inch high curb to protect the dispensers. |
| 12/14/2011 | TERRY STEVENS | ZONING | REVIEW | Denied | 10/27/2011 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. |