Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11BU01343
Parcel: 12703001A

Review Status: Completed

Review Details: TANKS

Permit Number - T11BU01343
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Provide cut sheets for the tanks, piping, and dispensers indicating the UL or other listing per IFC Section 2206.

Detail 5 on Sheet F3.2 must be corrected to show the bollards comply with IFC Section 312 for the four foot spacing or provide a six inch high curb to protect the dispensers.
11/03/2011 SREEVES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/03/2011 SREEVES1 ZONING REVIEW Needs Review