Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T11BU01341
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Provide cut sheets for the tanks, piping, and dispensers indicating the UL or other listing per IFC Section 2206. Detail 5 on Sheet F3.2 must be corrected to show the bollards comply with IFC Section 312 for the four foot spacing all the way around the dispensers or provide a six inch high curb to protect the dispensers. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/26/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 01/26/2012 | SUE REEVES | REJECT SHELF | Completed |